TECHNICAL DATA: | |
Temperature control | self-optimizing, electronic microprocessor controller MP-888 with digital display of the set and actual value. Automatic temperature monitoring. |
Flow control | electronically, with digital display and automatic control of the minimum flow. |
Cooling capacity Nominal |
54 kW – see diagram |
Temperature range Circulating water Air temperature |
+10°C up to +40°C +2°C up to +45°C |
Heating | 12 kW, manual switchable |
Content water tank | approx. 250 l |
Refrigerating agent | R-134a |
Pump capacity | max. 6.2 bar / max. 250 l/min – see pump diagram |
Compressor | hermetically sealed |
Condenser | air cooled, air inlet located on the rear, blow out located on the side/top |
Air volume | 8’000 m3/h (not relevant to WK) |
Power consumption | approx. 18 kW (heating mode approx. 18 kW, cooling mode approx. 14 kW) |
Connections To mould From mould Automatic water refill Drain Cooling water in/out |
1 1/4″ BSP female thread 1 1/2″ BSP female thread 3/8″ BSP female thread 1″ BSP female thread 1″ BSP female thread (only at WK) |
Dimensions (L×W×H) | 1’350 × 1’050 × 1’950 mm, incl. castors |
Noise Level(in 3 m distance) | 65 dBA |
Weight | 585 kg empty |
Color | silvergrey RAL 7001 |
Also Available:
TT-54’500 WK:
The same model is also available as water cooled version.
Required cooling water: minimum 1,5 bar water pressure.
With cooling tower water (approx. 30°C) approx. 65 l/min cooling water consumption
With tap water (approx. 10 – 15°C) approx. 25 – 40 l/min cooling water consumption
There are no reviews yet.