TECHNICAL DATA: | |
Cooling capacity Nominal Actual capacity in practice |
approx. 60 kW 12 kW at -10°C (see diagram) |
Temperature range | 0°C up to -25°C with water-glycol mixture not suitable for temperatures from +10°C up to + 40°C |
Refrigerating agent | R-404a |
Water tank capacity | approx. 150 litres |
Temperature control | electronic temperature controller MP-888 with digital display set and actual temperatures. |
Electronic flow control | option |
Pump capacity | max. 4,8 bar / max. 140 l/min. – at 100 l/min. 3,0 bar (see diagram) |
Pump motor | 1,5 kW |
Compressor | hermetically sealed |
Condenser needed cooling water, min. 1,5 bar with cooling tower water ca. 30°C with netwater approx. 10 – 15°C |
water cooled
approx. 60 – 100 l/min water consumption |
Power consumption | approx. 15 kW |
Connections To/ from mould Cooling water in/out Automatic water refill |
1” female thread 1” female thread 3/8” female thread |
Dimensions (L×W×H) | 1’100 x 790 x 1’660 mm, incl. castors |
Noise Level (in 3 m distance) | 73 dBA |
Weight | approx. 400 kg empty (filled approx. 580 kg) |
Color | silvergrey RAL 7001 |
TT-29’000 WK
TT-29’000 WK
Water Chiller
For water temperatures from -25°C up to 0°C,
with water-glycol mixture
water cooled condensor
For water temperatures from -25°C up to 0°C,
with water-glycol mixture
water cooled condensor
There are no reviews yet.