TECHNICAL DATA: | |
Temperature control | self-optimizing, electronic microprocessor controller MP-888 with digital display of the set and actual value. Automatic temperature monitoring. |
Flow control | electronically, with digital display and automatic control of the minimum flow. |
Cooling capacity Nominal |
216 kW – see diagram |
Temperature range Circulating water Air temperature |
+10°C up to +40°C +2°C up to +45°C |
Content water tank | approx. 600 l |
Refrigerating agent | R-134a |
Pump capacity External circuit Internal circuit |
at 200 l/min 5 bar; at 400 l/min 3,5 bar approx. 500 l/min |
Compressor | hermetically sealed |
Condenser | air cooled, air inlet located on the rear, blow out located on the side/top |
Air volume | 4 x 8’000 m3/h (not relevant to WK) |
Power consumption | approx. 66 kW |
Connections To / from mould Automatic water refill Drain Cooling water in/out |
2″ BSP female thread 3/8″ BSP female thread 1″ BSP female thread 2″ BSP female thread (only at WK) |
Dimensions (L×W×H) | 3’350 × 1’300 × 2’090 mm, incl. feets |
Noise Level(in 3 m distance) | 70 dBA |
Weight | 2’040 kg empty |
Color | silvergrey RAL 7001 |
Also Available:
TT-216’000 WK:
The same model is also available as water cooled version.
Required cooling water: minimum 1,5 bar water pressure.
With cooling tower water (approx. 30°C) approx. 260 l/min cooling water consumption
With tap water (approx. 10 – 15°C) approx. 100 – 150 l/min cooling water consumption
There are no reviews yet.